Data Channel Usage

How does the type of connected ZETSENSOR affect data channel usage of the measuring line to which it is connected?

Effect of the Digital Sensor Type And Selected Data Output Frequency On Usage (In Percent) Of Data Channel With Rs485 Interface For Data Rates 19.2, 57.6 and 115.2 Kbps
Module type Frequency of data output (Hz) Data rate of RS 485 interface (Kbps)
19.2 57.6 115.2
ZET7010,
ZET7010 DS,
ZET7010 DT,
ZET7012-A,
ZET7012-I
5
10
25
50
125
2.4%
4.8%
12%
24%
60%
0.8%
1.6%
4%
8%
20%
0.4%
0.8%
2%
4%
10%
ZET7020 1
4
0.48%
1.92%
0.16%
0.64%
0.08%
0.32%
ZET7021 10
62
4.8%
28.8%
1.6%
9.6%
0.8%
4.8%
ZET7050,
ZET7051,
ZET7060-E,
ZET7060-S
10 4.80% 1.60% 0.80%
ZET7052,
ZET7061
10 14.40% 4.80% 2.40%
ZET7054 1
10
100
500
0.96%
9.6%
96%
unrealizable
0.32%
3.2%
32%
unrealizable
0.16%
1.6%
16%
90%
ZET7060-G,
ZET7090
10 9.60% 3.20% 1.60%
ZET7060 1
10
50
100
200
0.48%
4.8%
24%
48%
96%
0.16%
1.6%
8%
16%
32%
0.08%
0.8%
4%
8%
16%
ZET7080-I,
ZET7080-V
10
100
400
4.8%
48%
unrealizable
1.6%
16%
64%
0.8%
8%
32%
Effect Of the Digital Sensor Type And Selected Data Output Frequency On Usage (In Percent) Of Data Channel With CAN Interface For Data Rates 100, 300 and 1000 Kbps
Module type Frequency of data output (Hz) Data rate of CAN interface (Kbps)
100 300 1000
ZET7110,
ZET7110 DS,
ZET7110 DT,
ZET7112-A,
ZET7112-I
5
10
25
50
125
0.5%
1%
2.5%
5%
12.5%
0.17%
0.34%
0.84%
1.67%
4.17%
0.05%
0.1%
0.25%
0.5%
1.25%
ZET7111,
ZET7111-L
50
250
625
1,250
5%
25%
62.5%
unrealizable
1.7%
8.4%
20.84%
41.7%
0.5%
2.5%
6.25%
12.5%
ZET7120 1
4
0.1%
0.4%
0.04%
0.14%
0.01%
0.04%
ZET7121 10
50
1%
5%
0.34%
1.7%
0.1%
0.5%
ZET7140-S 50
100
500
1,000
5,000
10,000
5%
10%
50%
100%
unrealizable
unrealizable
1,7%
3,4%
16,7%
33,4%
unrealizable
unrealizable
0,5%
1%
5%
10%
50%
100%
ZET7140-E up to 2,000 depends on frequency of recorded events
ZET7140-R,
ZET7160-E
1
10
100
0.1%
1%
10%
0.04%
0.34%
3.4%
0.01%
0.1%
1%
ZET7141 up to 2,000 depends on frequency of recorded events
ZET7150 10
100
400
1%
10%
40%
0.34%
3.4%
13.4%
0.1%
1%
4%
ZET7151
BC 314
10
500
1,000
2,000
4,000
8,000
12,000
1%
50%
100%
unrealizable
unrealizable
unrealizable
unrealizable
0.34%
16.7%
33.4%
66.7%
unrealizable
unrealizable
unrealizable
0.1%
5%
10%
20%
40%
80%
unrealizable
ZET7152 10
800
3%
unrealizable
1%
80%
0.3%
24%
ZET7154 1
10
100
500
0.2%
2%
20%
100%
0.07%
0.67%
6.7%
33.4%
0.02%
0.2%
2%
10%
ZET7160 100
500
1,000
1,500
2,000
10%
50%
100%
unrealizable
unrealizable
3.4%
16.7%
33.4%
50%
67.7%
1%
5%
10%
15%
20%
ZET7160-S,
ZET7160-RS,
ZET7160-R,
ZET7191,
ZET7175,
ZET7178
10 1% 0,34% 0,10%
ZET7160-G,
ZET7190,
ZET7190-R
10 2% 0.67% 0.20%
ZET7161 10 3% 1% 0.30%
ZET7180-I,
ZET7180-V
10
100
400
1%
10%
40%
0.34%
3.4%
13.3%
0.1%
1%
4%

Data rate between fragments of measuring network through a segment created on a radio channel with ZET 1772M and ZET 7152S modules – not more than 600 counts per second.
Data rate through GSM channel created with ZET 7177 module is not more than 200 counts per second.